Specification: |
| MODEL | JTX |
INPUT | AC Input Voltage Range | Universal input 150~ 265VAC. |
Operating Frequency Range | 47Hz to 63 Hz |
Rated Current | <4A |
Inrush Current | <20A |
Leakage Current | <10mA |
OUTPUT | Rated DC Output Voltage | -48V DC |
Output voltage range | 42V~58V |
Float charge voltage | 53.5V |
Boost charge voltage | 56.5V |
Rated Current | 7A |
Voltage regulation | ±0.5% |
Ripple & Noise(MAX.) | <300mV |
Efficiency(TYP.) | >85% |
(intput side) PROTECTION | Protected against high output voltage | AC 145v~150Vac |
Protected against low output voltage | AC 265v~270Vac |
| |
(output side) PROTECTION | Protected against short circuit | |
Protected against reverse polarity | |
Protected against high output voltage | 57v~62v |
Protected against low output voltage | 42v~44v |
Protected against high Temperature | |
Measurement of | Individual module AC input current | |
Individual module AC input voltage | |
Individual module DC output current | |
Individual module DC output voltage | |
Battery charging/discharging current | |
ENVIRONMENT | Temperature | -40℃—55℃ |
Humidity | 5%—95% |
Altitude | 3000M |
M.T.B.F. | ≥ 88Khour |
SAFETY | EN60950-1 UL60950-1 TUV |
EMC | EMI Standards | CLASS A |
EMS Standards | CLASS A |
OTHERS | Cooling | Forced ventilation |
Major fault alarms(audio and visual)in a system like output fuse failure,battery fuse shall be provided |
The individual module shall be capable of running in stand-alone mode as well as in parallel mode. When operating in parallel mode it shall have a facility of load sharing (ie. difference between sharing current of the modules shall be within 10% of rated output current) between the rectifier modules in a system. |
The modules shall have current limit facility adjustable from 25% - 100% of rated output current. |
The module shall have soft start facility during starting period. |